Sunday 18 January 2015

CHAPTER 2 -LITERATURE REVIEW-

CHAPTER 2 (week 5 -research )
LITERATURE REVIEW

This paper that was published by Newagepublisher.com titled Auto Re-Closing says that It is well realized that the transient faults which are most frequent in occurrence do no permanent damage to the system as they are transitory in nature. These faults disappear if the line is disconnected from the system momentarily in order to allow the arc to extinguish. After the arc path has become sufficiently deionized, the line can be reclosed to restore normal service. The type of fault could be a flashover across an insulator. Reclosing could also achieve the same thing with semi-permanent faults but with a delayed action, e.g., a small tree branch falling on the line, in which case the cause of the fault would not be removed by the immediate tripping of the circuit breaker but could be burnt away during a time delayed trip and thus the line reclosed to restore normal service. Now should the fault be permanent, reclosing is of no use, as the fault still remains on reclosing and the fault has to be attended personally. It simply means that if the fault does not disappear after the first trip and closure, double or triple-shot reclosing is used in some cases before pulling the line out of service.

Experience shows that nearly 80% of the faults are cleared after the first trip, 10% stay in for the second reclosure which is made after a time delay, 3% require the third reclosure and about 7% are permanent faults which are not cleared and result in lockout of the reclosing relay. When a line is fed from both ends, the breakers at the two ends trip simultaneously on occurrence of the fault, the generators at the two ends of the line drift apart in phase, the breakers must be reclosed before the generators drift too far apart for synchronism to be maintained, such a reclosure increases the stability limit considerably.

In present day power systems, automatic reclosing finds wide application. It therefore follows that to effect fault clearance and subsequent reclosure, it is often necessary to operate sequentially several items of switchgear. Recently logical design principles have been applied for the control of autoreclose switching sequences in large substations. The obvious advantages are continuous supply except for short duration when tripping and reclosure operations are being performed, this renders the substation unattended. The success of rapid reclosure to a large extent depends on the speed of operation of the protections. This is so because high speed protection decreases the amount of damage incurred and thus increases the probability of successful operation.
In some cases application of automatic reclosing enables us to use very simple but high speed protections of the lines. With instantaneous protection being applied indiscriminate tripping of several circuit breakers is possible but the provision of auto-reclose makes it a selective operation. is essential that the system dead time be kept to a few cycles so that the generators do not drift apart. High speed protection such as pilot wire carrier or distance must be used to obtain operating times of one or two cycles. It is therefore desired that the reclosure be of the single shot type. High speed reclosure in high voltage circuits improves the stability to a considerable extent on single-circuit ties.
Overcurrent protection with in turn automatic reclosure is enables us to realize high-speed protection of every section against transient as well as permanent faults. This is achieved by installing high speed nonselective overcurrent protections at all head parts of the sections. The pickup value for all such protections is selected for faults inside the full length of the given section and not for faults beyond the step down transformers if one such exists. Different zones of protection. Any nonselective operation of faults outside the given section is corrected by automatic reclosing. When the line is protected by composite overcurrent protection, the first stage of the protection can be employed as high speed nonselective overcurrent protection. Consider a permanent fault of system). The high speed relays of breakers 1 and 2 will operate. Practically immediately the automatic recloser circuit ties subjected to single circuit faults the continuity through the healthy circuit prevents the generators from drifting apart so fast and increase in the stability limit is thus moderate. Nevertheless, it is sometimes important. However, when the faults occur simultaneously on both the circuits the stability limit increases again considerably.



line are opened after fault incidence, independent of the fault type, and are reclosed after a predetermined time period following the initial circuit breaker opening. For a single circuit interconnectors between two power systems, the opening of all the three phases of the circuit breaker makes the generators in each group start to drift apart in relation to each other, since no interchange of synchronizing power can take place.
On the other hand single-phase auto-reclosure is one in which only the faulted phase is opened in the presence of a single-phase fault and reclosed after a controlled delay period. For multiphase faults, all three phases are opened and reclosure is not attempted. In case of single-phase faults which are in majority, synchronizing power can still be interchanged through the healthy phases. In the case of single-phase auto-reclosing each phase of the circuit breaker has to be segregated and provided with its own closing and tripping mechanism. Also it is necessary to fit phase selecting relays that will detect and select the faulty phase. Thus single-phase auto-reclosing is more complex and expensive as compared to

three-phase auto-reclosing. When single-phase auto-reclose is used the faulty phase must be reenergized for a longer interval of time, than in the case of three-phase auto-reclose, owing to the capacitive coupling between the faulty phase and the healthy conductors which tends to increase the duration of the arc. The advantage claimed for single-phase reclosing is that on a system with transformer neutrals grounded solidly at each substation, the interruption of one phase to clear a ground fault causes negligible interference with the load because the interrupted phase current now flows in the ground through neutral points until the fault current is cleared and the faulted phase reclosed. The main drawback is its longer deionizing time which can cause interference with communication circuits and, in certain cases may operation of earth relays in double circuit lines owing to the flow of zero sequence currents.

No comments:

Post a Comment