This paper that was published
by Newagepublisher.com titled Auto Re-Closing review that the
transient faults which are most frequent in occurrence do not cause permanent
damage to the system as they are transitory in nature. These faults disappear
if the line is disconnected from the system momentarily in order to allow the
arc to extinguish. After the arc path has become sufficiently deionized, the
line can be reclosed to restore normal service. The type of fault could be a
flashover across an insulator. Reclosing could also achieve the same thing with
semi-permanent faults but with a delayed action, e.g., a small tree branch
falling on the line, in which case the cause of the fault would not be removed
by the immediate tripping of the circuit breaker but could be burnt away during
a time delayed trip and thus the line reclosed to restore normal service. Now
should the fault be permanent, reclosing if no use, as the fault still remains
on reclosing and the fault has to be attended personally. It simply means that
if the fault does not disappear after the first trip and closure, double or
triple-shot reclosing is used in some cases before pulling the line out of
service.
Experience shows that nearly 80% of the faults are
cleared after the first trip, 10% stay in for the second reclosed which is made
after a time delay, 3% require the third reclosed and about 7% are permanent
faults which are not cleared and result in lockout of the reclosing relay. The
breakers at the two ends trip simultaneously on occurrence of the fault when a
line is fed from both ends. The generators at the two ends of the line will drift
apart in phase and the breakers must be reclosed before the generators drift
too far apart for synchronism to be maintained. This, the reclosed will increases
the stability limit [7].
In present
day power systems, automatic reclosing finds wide application. It therefore
follows the effects of fault clearance and subsequent reclosed, hence it is
often necessary to operate sequentially several items of switchgear. Recently
logical design principles have been applied for the control of auto reclosed
switching sequences in large substations. The obvious advantages are the continuous
supply except for the short duration when tripping and reclosed operations are
being performed, this renders the substation unattended. The success of rapid reclosed
to a large extent depends on the speed of operation of the protections. This is
because high speed protection decreases the amount of damage incurred and thus
increases the probability of successful operation [7].
In
some cases application of automatic reclosing enables us to use very simple but
high speed protections of the lines. During the instantaneous protection being
applied, indiscriminate tripping of several circuit breakers is possible but
the provision of auto-reclose makes it a selective operation. It is essential
that the system dead time be kept to a few cycles so that the generators do not
drift apart. High speed protection such as pilot wire carrier or distance must
be used to obtain operating times of one or two cycles. It is therefore desired
that the reclosed to be of the single shot type. High speed reclosed in high
voltage circuits improves the stability to a considerable extent on
single-circuit ties. [7]
Overcurrent
protection with in turn cause automatic reclosed is enables to create high-speed
protection of every section against transient as well as permanent faults. This
is achieved by installing high speed nonselective overcurrent protections at
all head parts of the sections. The pickup value for all such protections is
selected for faults inside the full length of the given section and not for
faults beyond the step down transformers if it is exists in different zones of
protection. Any nonselective operation of faults outside the given section is
corrected by automatic reclosing. During the protection of line by composite
overcurrent protection, the first stage of the protection can be employed as
high speed nonselective overcurrent protection. Practically, the automatic reclosed
circuit immediately ties subjected faults to single circuit faults. The
continuity through the healthy circuit prevents the generators from drifting
apart so fast and the stability limit is therefore increased. However, when the
faults occur simultaneously on both the circuits the stability limit also will
be increases [7].
Line
will be opened after fault incidence, independent of the fault type and are
reclosed after a predetermined time period following the opening of initial
circuit breaker. For a single circuit interconnectors between two power
systems, the opening of all the three phases of the circuit breaker makes the
generators in each group start to drift apart in relation to each other, since
no interchange of synchronizing power can take place. [7]
On
the other hand single-phase auto-reclosed is one in which only the faulted
phase is opened during the presence of the single-phase fault and reclosed
after a controlled delay period. For multiphase faults, all three phases that are
opened and reclosed are not attempted. In case of the single-phase faults,
synchronizing power can still be interchanged through the healthy phases. In
the case of the single-phase auto-reclosing, each phase of the circuit breaker
has to be segregated and provided with its own closing and tripping mechanism.
Also it is necessary to fit phase selecting relays that will detect and select
the faulty phase. Thus, single-phase auto-reclosing is more complex and
expensive as compared to three-phase auto-reclosing. [7]
During
the usage of single-phase auto-reclosed, the faulty phase must be reenergized
for a longer interval of time. In the case of three-phase auto-reclose, owing
to the capacitive coupling between the faulty phase and the healthy conductors must
be done to increase the duration of the arc. The advantage claimed for
single-phase reclosing is that (system with transformer neutrals grounded
solidly at each substation), the interruption of one phase to clear a ground
fault causes negligible interference with the load. This is because the
interrupted phase current now flows in the ground through neutral points until
the fault current is cleared and the faulted phase reclosed. The main drawback
is it has longer deionizing time which can cause interference with communication
circuits and in certain cases the operation of earth relays in double circuit
lines owing to the flow of zero sequence currents [7].
Another paper is from Charles J.Nochumson from website www.eaton.com.
This paper review on the application of new technologies in power circuit
breaker with high interrupting capacity and short time rating. It brief on the
description of an available classes of low voltage circuit breakers.
The Low Voltage Power Circuit Breakers (LVPCBs) are rated
and tested to ANSI C37 standards. They are mainly used in Low Voltage Metal
Enclosed Draw out Switchgear and built based on ANSI C37 standards. LVPCBs
offer field maintainability of main contacts, operating mechanism, and arc
chute replacement. LVPCBs are tested in the enclosure and are rated for 100%
applications. They offer two steps for stored energy closing mechanisms, which
have typical opening or closing times of three to five cycles. For electrical
operation, they are typically combined with an internal motor to change the
breaker closing springs and solenoids to release the spring stored energy for
closing and opening of the breaker.
It was typically applied in systems with selective
coordination, synchronizing schemes and automatic transfer scheme applications.
Molded Case Circuit Breakers (MCCBs) are tested according to UL489. They are
typically applied in Low Voltage Switchboards, Motor Control Centers and Panel boards.
MCCB current carrying parts, mechanism and trip devices are completely placed
within a molded case, and are not designed to be field maintainable. MCCBs as
standard are tested in open air and are de-rated to 80% when placed in an
enclosure. Optional MCCBs are available which have been UL tested for
applications at 100% in the enclosure. Molded case circuit breakers have
over-center toggle operating mechanisms.
For electrical operation, they are typically combined
with external motor operating mechanisms, which move the breaker handle. The
external motor operator is not fast enough for synchronizing or automatic
transfer scheme applications. MCCBs are also available in current-limiting
type. Insulated Case Circuit Breakers (ICCBs) also is rated and tested in
according to UL489. They are typically applied as mains in Low Voltage
Switchboards, Motor Control Centers and some transfer switches. Similar to the
MCCB, the ICCB is generally placed in a sealed molded case, and it is not
designed to be fully field maintainable. ICCBs are found as either 80% rated
devices or 100% rated devices when mounted in the proper enclosure. ICCBs
utilize two step stored energy mechanisms, similar to LVPCBs. ICCBs are
normally not fast enough to qualify as current-limiting type.
No comments:
Post a Comment