1.1 INTRODUCTION
Power system protection is the most important requirement
in the industrial or domestic electrical to prevent equipment from damage due
to fault. It is the fact of life that different types of faults occur on
electrical systems, however infrequently, and at random locations. Faults can
be broadly classified into two main areas which are designated as Active and
Passive.
1.1.1 Active Fault
The Active fault is when actual current flows from one
phase conductor to another (phase-to-phase) or alternatively from one phase
conductor to earth (phase-to-earth). This type of fault can also be further
classified into two areas, namely the “solid” fault and the “incipient” fault.
The solid fault occurs as a result of an immediate complete breakdown of
insulation as would happen if, say, a pick struck an underground cable,
bridging conductors, or the cable was dug up by a bulldozer. In mining, a rock
fall could crush a cable as would a shuttle car. In these circumstances the
fault current would be very high, resulting in an electrical explosion. This
type of fault must be cleared as quickly as possible, otherwise there will be greatly
increased of damage at the fault location. This later will cause danger to
operating personnel (Flash products), danger of igniting combustible gas such
as methane in hazardous areas, giving rise to a disaster of horrendous
proportions, increased probability of earth faults spreading to other phases,
higher mechanical and thermal stressing of all items of plant carrying the
current fault. Particularly transformers windings will suffer progressive and
cumulative deterioration because of the enormous electromechanical forces
caused by multi-phase faults proportional to the current squared, sustained
voltage dips resulting in motor (and generator), instability that could leading
to extensive shut-down at the plant concerned and possibly other nearby plants.
The incipient fault, on the other hand, is a fault that
starts from very small beginnings, from say some partial discharge (excessive
electronic activity often referred to as Corona) in a void of the insulation.
It will increase and develop over an extended period, until such time as it
burns away adjacent insulation and eventually running away and develop into a
solid fault. Other causes can typically be a high-resistance joint or contact,
alternatively pollution of insulators causing tracking across their surface.
Once tracking occurs, any surrounding air will ionize which then behaves like a
solid conductor consequently creating a solid fault.
1.1.2
Passive Fault
Passive faults are not real faults in the true sense of
the word but are rather conditions that are stressing the system beyond its
design capacity, so that ultimately active faults will occur.
Figure 1 : Type of fault
Typical examples are overloading - leading to overheating
of insulation (deteriorating quality, reduced life and ultimate failure),
overvoltage - stressing the insulation beyond its limits, under frequency -
causing plant to behave incorrectly and power swings - generators going out of step
or synchronism with each other. It is therefore very necessary to also protect
against these conditions. Types of Faults on a Three Phase System that can occur on a
three phase A.C is shown in Figure 1.
As refer to Figure 1, the types of Faults on a
Three Phase System are:
(A) Phase-to-earth
fault
(B) Phase-to-phase
fault
(C)
Phase-to-phase-to-earth fault
(D) Three phase fault
(E) Three
phase-to-earth fault
(F) Phase-to-pilot
fault *
(G) Pilot-to-earth
fault *
* In
underground mining applications only
It will be noted that for a phase-to-phase fault, the
currents will be high, because the fault current is only limited by the
inherent (natural) series impedance of the power system up to the point of
faulty (refer Ohms law). By design, this inherent series impedance in a power
system is purposely chosen to be as low as possible in order to get maximum
power transfer to the consumer and limit unnecessary losses in the network
itself in the interests of efficiency. On the other hand, the magnitude of
earth faults currents will be determined by the manner in which the system
neutral is earthed. Solid neutral earthing means high earth fault currents as
this is only limited by the inherent earth fault (zero sequence) impedance of
the system. It is worth noting at this juncture that it is possible to control
the level of earth fault current that can flow by the judicious choice of
earthing arrangements for the neutral. In other words, by the use of Resistance
or Impedance in the neutral of the system, earth fault currents can be
engineered to be at whatever level is desired and are therefore controllable.
This cannot be achieved for phase faults.
1.1.3 Transient &
Permanent Faults
Transient faults are faults which do not damage the
insulation permanently and allow the circuit to be safely re-energized after a
short period of time. A typical example would be an insulator flashover
following a lightning strike, which would be successfully cleared on opening of
the circuit breaker and later could automatically re-closed. Transient faults
occur mainly on outdoor equipment where air is the main insulating medium. Permanent
faults, as the name implies, are the result of permanent damage to the insulation.
In this case, the equipment has to be repaired and reclosing must not be entertained.
1.1.4
Symmetrical & Asymmetrical Faults
A symmetrical fault is a balanced fault with the
sinusoidal waves being equal about their axes, and represents a steady state
condition. An asymmetrical fault displays a d.c. offset, transient in nature
and decaying to the steady state of the symmetrical fault after a period of
time:
Figure 2 : Steady State
Graph
The amount of offset
depends on the X/R (power factor) of the power system and the first peak can be
as high as 2.55 times the steady state level. Figure 2 shows the steady state
graph.
1.1.5 Electrical Faults
A
fault is any abnormal situation in an electrical system in which the electrical
current may or may not flow through the intended parts. Equipment failure also
attributable to some defect in the circuit such as loose connection, insulation
failure or short circuit etc. The type of faults in a distribution network that
is detected by an ELCB is:
i. Over-Current Fault
ii. Short-Circuit Fault
iii. Lightning Fault
1.1.6
Over-current Fault
The
National Electrical Code defines over current as any current in excess of the
rated current of equipment or the amp city of a conductor. It may result from
overload, short circuit, or ground fault. Current flow in a conductor always
generates heat. The greater the current flow, the hotter the conductor. Excess
heat is damaging to electrical components. For that reason, conductors have a
rated continuous current carrying capacity or amp city. Over current protection
devices are used to protect conductors from excessive current flow. These
protective devices are designed to keep the flow of current in a circuit at a
safe level to prevent the circuit conductors from overheating. In term of
over-current fault, the fuse or wire may melt or damage the other elements of
the circuit when a current greater than that which a circuit or a fuse is
designed to carry [2].
.
1.1.7 Short-Circuit Fault
A
short circuit in an electrical circuit is one that allows a current to travel along
different path from the one originally intended. The electrical opposite of a
short circuit is an “open circuit”, which is an infinite resistance between two
nodes. It is an abnormal low-resistance connection between two nodes of an
electrical circuit that are meant to be at different voltages. This results in
an excessive electric current (over-current) and potentially causes circuit
damage, overheating, fire or explosion [2].
Although
usually the result of a fault, there are cases where short circuits are caused
intentionally, for example for the purpose of voltage-sensing crowbar circuit
protectors. In circuit analysis, the term short circuit is used by analogy to
design at a zero-impedance connection between two nodes. This forces the two
nodes to be at the same voltage. In an ideal short circuit, this means there is
no resistance and no voltage drop a cross the short. In a simple circuit
analysis, wires are considered to be shorts. In real circuits, the result is a
connection of nearly zero impedance, and almost no resistance [2].
.
1.1.8 Lightning Fault
Lightning
is the visible discharge of static electricity within a cloud, between clouds,
or between the earth and a cloud. Scientists still do not fully understand what
causes lightning, but most experts believe that lightning is caused due to different
kinds of ice interact in a cloud. Updraft in the clouds separate charges, so
that positive charges flow towards the top of the cloud and the negative
charges flow to the bottom of the cloud. When the negative charges moves
downwards, a “stepped leader” is created. The leader rushes toward the earth in
150-foot discrete steps, producing an ionized path in air. The major part of
the lightning discharges current is carried in the return stroke, which flows
along the ionized path. One of the temporary faults is cause by direct
lightning phenomena. The example of permanent fault can mostly been seen on
electrical equipment [2].
1.2 Operation of ELCB Trip Situation
There
are two types of fault normally detected by ELCB, which are permanent fault and
temporary fault [2].
1.2.1 Permanent Failure or Permanent Damage
It is
usually trip when there is any leakage current in the circuit to earth or
ground. For permanent failure, the damaged must to repair first or remove the
damage from current before ELCB can be triggered again. If the damage has not been
repaired or removed from the circuit, it will trip again when the ELCB is
automatically triggered. If this happen many times, it will damage the ELCB [2].
1.2.2 Temporary Failure or Temporary Damage
It
can automatically trigger ELCB without need to repair or remove the damage from
supply circuit. If usually lightning and over loading occurs in resident or
industrial, it can give more problems to user to automatically trigger by
itself. For example is lightning occurrence [2].
1.2.3 Earth Leakage Circuit
Breaker (ELCB)
An
Earth Leakage Circuit Breaker (ELCB) is a device used to directly detect
currents leaking to earth from an installation and cut the power. It was mainly
used in TT earthing systems. In a TT earthing system, the protective earth
connection of the consumer is provided by a local connection to earth,
independent of any earth connection at the generator. The big advantage of the
TT earthing system is the fact that it is clear of high and low frequency
noises that come through the neutral wire from various electrical equipment
connected to it. This is why TT has always been preferable for special
applications like telecommunication sites where the benefit from the
interference-free earthing can be obtained. Also, TT does not have the risk of
a broken neutral. In locations where power is distributed overhead and TT is
used, installation of earth conductors are not at risk if there is any overhead
distribution conductor be fractured by, say, a fallen tree or branch [3].
Earth
Leakage Circuit Breaker (ELCB) operates by measuring the current balance
between two conductors using a differential current transformer. The device
will open its contacts when it detects any difference in current between the
line conductor and the neutral conductor. The supply and return current must
sum to zero, otherwise there is a leakage of current to somewhere else (to
earth/ground, or to another circuit, etc.). ELCB is designed to prevent
electrocution by detecting the leakage current, which can be far smaller
(typically 5-30 mill amperes) than the currents needed to operate conventional
circuit breakers or fuses (several amperes). RCD (Residential Current Device)
are intended to operate within 25-40 milliseconds before electric shock can
drive the heart into ventricular fibrillation, the most common cause of death
through electric shock [2].
In
the United States, the National Electrical Code requires GFCI (Ground Fault
circuit Interrupter) devices to protect people by interrupt the circuit if the
leakage current exceeds a range of 4-6 mA of current (the trip setting is
typically 5 mA) within 25 milliseconds. ELCB devices which protect equipment
(not people) are allowed to trip as high as 30 mA of current. In Europe, the
commonly used RCD have trip currents of 10-300 mA. Residual current detection
is complementary to over-current detection. Residual current detection cannot
provide protection for overload or short-circuit currents [2].
ELCB
with trip currents as high as 500 mA are sometimes deployed in environments
(such as computing centers) where a lower threshold would carry unacceptable
risk of accidental trips. These high-current ELCB serve more as an additional
fire-safety protection than as an effective protection against the risks of
electrical shocks. For many years, the voltage operated ELCB and the
differential current operated ELCB were both referred to as ELCB because it was
a simpler name to remember. However, the use of a common name for two different
devices gave rise to considerable confusion in the electrical industry. If the
wrong type was used on an installation, the level of protection given could be
substantially less than that intended. The ELCB is an important equipment to
install at each of house, hospital, factory, or every place that need the power
supply [2].
In
pre-RCD (residual Current device) era, the TT earthing system was unattractive
for general use because of its worse capability of accepting high currents in
case of a live-to-PE (Protective earth) short circuit (in comparison with TN
systems). But as residual current devices mitigate this disadvantage, the TT
earthing system becomes attractive for premises where all AC power circuits are
RCD-protected. The RCD is an electrical wiring device that disconnects a circuit
whenever it detects the electric current is not balanced between the phase
conductor and the neutral conductor. Such an imbalance is sometimes caused by
current leakage through the body of a person who is grounded and accidentally
touching the energized part of the circuit [2].
ELCB
has become one of the home safety systems in our life today. ELCB has reset
button which is to reclosed circuit breaker when the tripping occur. Today,
many of people busy with work and usually not at home. The problem will occur during
the over current, short circuit or current leakage at live conductor, it can
trip the circuit breaker “OFF” and cut off the whole power supply. This
situation can make certain important component or equipment cannot be
operated. In most household, ELCB need
to be reclosed manually during tripping, hence it is a troublesome thing for
user who is not at home and it might take a long time to reset back the button
of the circuit breaker. The main mechanism in operation is tripping coil which
is it can operate either in live or off condition. This ELCB will operate when
current is exceeding the rating of the current ELCB. These high currents will
not flows into equipment after ELCB tripped. It will flow directly into ground
by using ground rod. This ground rod must have the lower resistance to ensure
an easy flowing of high current. There are two types of ELCB [2]:
i. Voltage Earth Leakage Circuit Breaker (vELCB)
ii. Current Earth Leakage Circuit Breaker (iELCB)
1.2.3.1 Voltage Earth Leakage Circuit Breaker
(vELCB)
vELCB
is stand for the voltage operated circuit breaker. The device will function
when the current passes through the ELCB. vELCB contains relay loop which it
being connected to the metallic load body at one end and it is also connected
to ground wire at the other end. If the voltage of the load body is rise which
could cause the difference between earth and load body voltage, the danger of
electric shock will occur. This voltage difference will produce an electric
current from the load metallic body that passes through the relay loop and to
earth. When voltage on the load metallic body raised to the danger level which
exceed to 50Volt, the flowing current through relay loop could move the relay
contact by disconnecting the supply current in order to avoid from any electric
shock danger [2].
1.2.3.2 Current Earth Leakage Circuit Breaker
(iELCB)
iELCB
is stand for the current operated circuit breaker. Current-operated ELCBs are
generally known today as RCD (residual current device). iELCB also will protect
the load against earth leakage, even though the details and method of operation
are different. The device will be functioning when the current passes through
ELCB. This current admitted to current transform device and on the load.
Current from the load also admitted again to transform device. In normal state,
total current applied to the load is equal with the total current out of the
load. Due to the in and out of current are in balance, it does not affect the
current transform device. If there is any earth current leakage caused by earth
damage, then the in and out current will no longer in balance. This unbalance
current phenomenon will generate the current and if the current exceeded the
prescribed rate, the ELCB will jerked and cut off the supply. The device also
being called RCD, Residual Current Device in IEC or RCCB, Residual Current
Circuit Breaker [2].
1.3 Scope
of Project
In
Malaysia it is common, The faults might be LG (Line to Ground), LL (Line to
Line), 3L (Three lines) in the supply systems and these faults in three phase
supply system can affect the power system. To overcome this problem a system is
built, which can sense these faults and automatically disconnects the supply to
avoid large scale damage to the control gears in the grid sub-stations. [2]
An Earth
Leakage Circuit Breaker (ELCB) is a safety device used in
electrical installations with high earth impedance to prevent shock. It
detects small stray voltages on the metal enclosures of electrical equipment,
and interrupts the circuit if any dangerous voltage is detected.
The ELCB is a
specialized type of latching relay that
has a building's incoming mains power connected through its switching
contacts so that
the ELCB disconnects the power in an earth leakage (unsafe) condition. The ELCB
detects fault currents from live to the earth
(ground) wire within the installation it protects. If sufficient voltage appears
across the ELCB's sense coil, it will switch off the power
and remain off until manually reset. A voltage-sensing ELCB does not sense
fault currents from live to any other earthed body.
This device has one advantage, they are less sensitive to
fault conditions, and therefore have fewer nuisance trips. This does not mean
it always do, as practical performance depends on installation details and the
discrimination could enhance the filtering in the ELCB. Therefore, by
electrically separating cable armor from the cable circuit protective
conductor, an ELCB can be arranged to protect against cable damage only, and
not trip on faults in down line installations.
Even though
ELCB is good but it has some limitations such as they do not detect faults that
do not pass current through the CPC (Circuit
Protective Conductor) to the earth rod.
They do not allow a single building system
to be easily split into multiple sections with independent fault protection due
to the facts that earthing systems are usually bonded to pipework.[1]
1.4 Objectives
The
objectives of this project are:
i.
To develop an automatic re-closed Earth
Leakage Circuit Breaker for fault in three phase system.
ii.
To develop the prototype automatic tripping
mechanism of permanent and temporary fault in three phase system
1.5 Problem
Statement
Earth
Leakage Circuit Breaker (ELCB) is one type of electrical equipment that used as
a protection device. The main purpose of this type of equipment is to cut off
the power when the problem occurred. The main problem is, if there is any fault
occurred and there is no human that can switch on the device again due to many
reasons. The device that been used is mechanical switch that must be activated
manually after the ELCB been tripped. The ELCB will stay off until the user
push it back to ON condition although the problem that occurred is temporary
fault and it occurred only in one millisecond. So, it is not working as
automatic device that can operate intelligently.
Automatic Earth Leakage Circuit Breaker (Auto-ELCB)
is the solution for the temporary trip since it is the main cause for tripping
in Malaysia. After the temporary fault such as lightning happened, the situation
will be back to normal as the installation of Auto-ELCB will automatically
re-closed the breaker and hence the power will be supplied continuously. However,
the Auto-ELCB will be permanently trip if the permanent fault occurred. The
owner needs to re-closed the Auto-ELCB manually by using this system.
Your Blog shares a valuable information about Power System Analysis and Short circuit analysis. It is very helpfull to detect the problems in short circuits.You warn the workers based on the international standards for personal protective equipment about Safety measurements in electrical hazards. To determine the short circuit currents is one of the most important aspects of designing power distribution systems. The effects of short circuits must be considered in selecting circuit protecting devices, Electrical equipment, Carrying out Arc Flash Analysis. The short circuit calculator is used to satisfy the need for a convenient, Comprehensive method of calculating fault currents. It is intended to Looped and radial low and medium voltage circuits. The calculator allows to Easily and Quickly obtain accurate potential short circuit currents at each node in a power distribution system. we are one of the top most Electrical hazard safety assessment consultants in the world.we provide services like Arc Flash Analysis, Short Circuit Analysis, Harmonic analysis, Relay coordination, etc, ....If you have any queries, Click on
ReplyDelete<"ahref="http://vbengg.com/short-circuit-analysis.html"> Power system protection and short circuit analysis <\a>